
Add to Cart
Features
-battery overcharge protection
-battery over-discharge protection
-output overload protection
-short-circuit protection
Parameter Table
Input voltage | 220-240 Vac 50/60Hz |
Input Current | 0.03A(Max) 230V AC |
Input Power | <4W |
Power Factor | ≥0.5@230Vac |
Battery charging current | 300mA(Max) |
Battery charging time | 24h(Max) |
Working humidity | 20-80%RH(No Condensation) |
Working temperature | -20-60°C |
Maximum shell temperature | 75°C |
Storage temperature | -20-40°C |
Electric strength | 3000Vac 5mA(input to output) |
IP Rating | IP20 |
Warranty | 3 Years |
LED Indicator
|
Yellow on
| The battery discharge time is insuffificient | Main power supply |
The yellow indicator blinks at 1Hz
| The battery is open circuit or the charging circuit is short-circuited | ||
The yellow indicator blinks at 3Hz
| The Led fifixture is open circuit , short circuit or no output when in the self-test state | ||
Red on
| Battery charging | ||
Red off
| Battery stop charging | ||
Green on
| In main power mode | ||
The green indicator blinks at 1Hz
| Monthly self-test status | ||
The green indicator blinks at 3Hz
| Annual self-test status | ||
The green indicator blinks two times
| Fast manual monthly/annual self-test | ||
LED indicator off
| Emergency status | Battery supply | |
The yellow indicator blinks at 3Hz |
The Led fifixture is open circuit ,short circuit,after 2 seconds,the output is turned off and the battery enters the standby state, need to reconnect the mains and then timing into normal operation
| ||
Yellow on
| Battery capacity is low | ||
Test button
| 1S<Key≦3S |
Green off,enter simulated emergency,maintain emergency status for 10S and exit
| Main power supply
|
3S<Key≦5S |
The green indicator blinks at 1Hz,enter the monthly self-test, maintain the emergency status for 120S and exit
| ||
5S<Key≦7S |
The green indicator blinks at 3Hz,enter the Annual self-test, keep to low battery voltage and exit
| ||
Double click |
The green indicator blinks two times,quickly view the monthly self-inspection and annual self-inspection, and automatically enter the annual self-inspection after 11 times of monthly inspection
| ||
3S<Key |
Exit the emergency state and enter the standby state,need to reconnect the mains and then timing into normal operation
| Battery supply |
Model Selection table
Model No. | Input voltage | Output voltage | Output Current | Lithium battery | Emergency time | Emergency power |
ES-EOE03-01S-120V | 220-240Vac 50/60Hz | 12-120V DC | 20-60mA | 3000mAh/3.7V | 3Hrs | 3W |
ES-EOE03-01S-200V | 220-240Vac 50/60Hz | 50-200V DC | 30-10mA | 3000mAh/3.7V | 3Hrs | 3W |
Dimension (Unit:mm)
Wiring Diagram
Cautions